Controls and Indications
Part No. 057-120 8660 OPERATING MANUAL ISSUE 1 07/05/2010 ADM
53
5.6 CONTROLS
Stop / Reset
This button places the module into its Stop/Reset mode. This will clear any alarm conditions for which
the triggering criteria have been removed. If the engine(s) is(are) running and the module is in Stop
mode, the module will automatically instruct the changeover device to unload the generator bus
(‘Close Bus becomes inactive (if used)). The start request is taken away. Should a remote start
signal be present while operating in this mode, a remote start will not occur.
Manual
This mode allows manual control of the functions. Once in Manual mode the module will respond to
the start button, sending a start request to the engine(s) over the MSC link. If the engine is running
off-load in the Manual mode and a remote start signal becomes present, the module will
automatically instruct the changeover device to place the generator bus on load (‘Close Bus becomes
active (if used)). Upon removal of the remote start signal, the generator bus remains on load until
either selection of the ‘STOP/RESET’ or ‘AUTO’ modes.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere in this
manual.
Auto
This button places the module into its ‘Automatic’ mode. This mode allows the module to control the
function of the system automatically. The module will monitor the remote start input and mains supply
status and once a start request is made, the set(s) will be automatically started and placed on load.
Upon removal of the starting signal, the module will automatically transfer the load from the generator
bus and shut the set(s) down observing the stop delay timer and cooling timer as necessary. The
module will then await the next start event. For further details, please see the more detailed
description of ‘Auto operation’ elsewhere in this manual.
Test
This button places the module into its ‘Test’ mode. This allows an on load test of the generator(s).
Once in Test mode the module will respond to the start button, sending a start request to the
engine(s) over the MSC link, and run on load, in parallel with the mains supply.
For further details, please see the more detailed description of ‘Test operation’ elsewhere in this
manual.
Start
This button is only active in TEST or MANUAL mode.
Pressing this button in manual or test mode will request the engines to start and run off load (manual)
or on load (test).
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the LEDs as a lamp test
feature.