Specification
13
3.8 COMMUNICATION PORTS
USB Port USB2.0 Device for connection to PC running DSE configuration suite only
Max distance 6m (yards)
Serial Communication RS232 and RS485 are both fitted but and provide independent operation
RS232 Serial port
Non – Isolated port
Max Baud rate 115200 baud subject to S/W
TX, RX, RTS, CTS, DSR, DTR, DCD
Male 9 way D type connector
Max distance 15m (50 feet)
RS485 Serial port
Isolated
Data connection 2 wire + common
Half Duplex
Data direction control for Transmit (by s/w protocol)
Max Baud Rate 115200
External termination required (120Ω)
Max common mode offset 70V (on board protection transorb)
Max distance 1.2km (¾ mile)
3.8.1 USB CONNECTION
The USB port is provided to give a simple means of connection between a PC and the controller.
Using the DSE Configuration Suite Software, the operator is then able to control the module, selecting
operating modes, etc.
Additionally, the various operating parameters (such as output volts, current, etc.) of the remote ATS
are available to be viewed or changed.
To connect a module to a PC by USB, the following items are required:
• DSE335 module
• DSE Configuration Suite PC Software
(Supplied on configuration suite software CD or available from
www.deepseaplc.com).
• USB cable Type A to Type B.
(This is the same cable as often used between a PC and a USB
printer)
DSE can supply this cable if required :
PC Configuration interface lead (USB type A – type B) DSE Part No
016-125
NOTE
NOTENOTE
NOTE:
: :
: The DC supply must be connected to the module for configuration by PC.
The DC supply must be connected to the module for configuration by PC.The DC supply must be connected to the module for configuration by PC.
The DC supply must be connected to the module for configuration by PC.
NOTE:
NOTE:NOTE:
NOTE:
Refer to DSE
Refer to DSERefer to DSE
Refer to DSE335
335335
335
Series Configuration Suite Manual (DSE part 057
Series Configuration Suite Manual (DSE part 057Series Configuration Suite Manual (DSE part 057
Series Configuration Suite Manual (DSE part 057-
--
-157
157157
157) for
) for ) for
) for
further details on configuring, monitoring and control.
further details on configuring, monitoring and control.further details on configuring, monitoring and control.
further details on configuring, monitoring and control.