Installation – Terminal Description
26
4.1.1 DC SUPPLY, OUTPUTS G-L
Pin No. Description Cable Size Notes
1
DC Plant Supply Input
(Negative)
2.5mm²
AWG 13
2
DC Plant Supply Input
(Positive)
2.5 mm²
AWG 13
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and
Output relays G,H,I, J, K & L
3 Output relay G
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
4 Output relay H
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
5 Output relay I
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
6 Output relay J
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
7 Output relay K
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
8 Output relay L
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
4.1.2 CONFIGURABLE DIGITAL INPUTS A-I
Pin No. Description Cable Size Notes
9 Configurable digital input A
0.5mm²
AWG 20
Switch to negative or positive depending on
configuration
10 Configurable digital input B
0.5mm²
AWG 20
Switch to negative or positive depending on
configuration
11 Configurable digital input C
0.5mm²
AWG 20
Switch to negative or positive depending on
configuration
12 Configurable digital input D
0.5mm²
AWG 20
Switch to negative or positive depending on
configuration
13 Configurable digital input E
0.5mm²
AWG 20
Switch to negative or positive depending on
configuration
14 Configurable digital input F
0.5mm²
AWG 20
Switch to negative or positive depending on
configuration
15 Configurable digital input G
0.5mm²
AWG 20
Switch to negative or positive depending on
configuration
16 Configurable digital input H
0.5mm²
AWG 20
Switch to negative or positive depending on
configuration
17 Configurable digital input I
0.5mm²
AWG 20
Switch to negative or positive depending on
configuration