Installation – Terminal Description
28
4.1.6 S1 VOLTAGE SENSING
Pin No. Description Cable Size Notes
S1
38 S1 L1 (R) voltage monitoring
1.0mm
AWG 18
Connect to S1 L1 (R) incoming supply (AC)
(Recommend 2A fuse)
39 S1 L2 (S) voltage monitoring
1.0mm
AWG 18
Connect to S1 L1 (S) incoming supply (AC)
(Recommend 2A fuse)
40 S1 L3 (T) voltage monitoring
1.0mm
AWG 18
Connect to S1 L1 (T) incoming supply (AC)
(Recommend 2A fuse)
41 S1 Neutral (N) input
1.0mm
AWG 18
Connect to S1 N incoming supply (AC)
NOTE:
NOTE:NOTE:
NOTE:
The above table describes connections to a three phase, four wire alternator.
The above table describes connections to a three phase, four wire alternator. The above table describes connections to a three phase, four wire alternator.
The above table describes connections to a three phase, four wire alternator.
For alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of
For alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of For alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of
For alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of
this manual.
this manual.this manual.
this manual.
4.1.7 LOAD CURRENT TRANSFORMERS
WARNING!:
WARNING!:WARNING!:
WARNING!:
Do not disconnect this plug when the
Do not disconnect this plug when the Do not disconnect this plug when the
Do not disconnect this plug when the CTs are carrying current.
CTs are carrying current. CTs are carrying current.
CTs are carrying current.
Disconnection will open circuit the secondary of the C.T.’s and dangerous voltages may
Disconnection will open circuit the secondary of the C.T.’s and dangerous voltages may Disconnection will open circuit the secondary of the C.T.’s and dangerous voltages may
Disconnection will open circuit the secondary of the C.T.’s and dangerous voltages may
then develop. Always ensure the CTs are not carrying current and the CTs are short circuit
then develop. Always ensure the CTs are not carrying current and the CTs are short circuit then develop. Always ensure the CTs are not carrying current and the CTs are short circuit
then develop. Always ensure the CTs are not carrying current and the CTs are short circuit
connected before making or breaking connections to t
connected before making or breaking connections to tconnected before making or breaking connections to t
connected before making or breaking connections to the module.
he module.he module.
he module.
NOTE:
NOTE:NOTE:
NOTE:
The module has a burden of 0.5VA on the CT. Ensure the CT is rated for the
The module has a burden of 0.5VA on the CT. Ensure the CT is rated for the The module has a burden of 0.5VA on the CT. Ensure the CT is rated for the
The module has a burden of 0.5VA on the CT. Ensure the CT is rated for the
burden of the controller, the cable length being used and any other equipment sharing the
burden of the controller, the cable length being used and any other equipment sharing the burden of the controller, the cable length being used and any other equipment sharing the
burden of the controller, the cable length being used and any other equipment sharing the
CT. If in doubt, consult your CT supplier.
CT. If in doubt, consult your CT supplier.CT. If in doubt, consult your CT supplier.
CT. If in doubt, consult your CT supplier.
Pin No. Description Cable Size Notes
42 CT Secondary for Load L1
2.5mm²
AWG 13
Connect to s1 secondary of L1 monitoring CT
43 CT Secondary for Load L2
2.5mm²
AWG 13
Connect to s1 secondary of L2 monitoring CT
44 CT Secondary for Load L3
2.5mm²
AWG 13
Connect to s1 secondary of L3 monitoring CT